    5
    ·
    2 days ago

    Actual paper (not calling this a study since this appears to be non–peer-reviewed and only self-published): https://microgridai.centrefornetzero.org/ Be advised that this website relies on some Chromium-only trickery.

    renewable microgrids […] compared to nuclear small modular reactors

    A 95% renewable microgrid with 5% gas backup - in line with the UK’s Clean Power 2030 target - was modelled at almost a third (31.7%) lower cost than scenario 1 in today’s prices. In this model, the gas is restricted to just under 80MW (2/3rds the size of the data centre) and the model correspondingly chooses a larger battery for storage, and increases the size of wind and solar technologies.

    I’m confused; how does 5% equal 2/3 the size of the data center modeled?

    (Edit: Someone else suggested this: “I think the gas can supply 2/3 of the power that the data centre requires for situations when there is no sun or wind but only makes up 5% of the total energy used over a year.”)

    They include a link to the model: https://github.com/ryanjenkinson/data-centre-modelling

    • Dharma Curious (he/him)@slrpnk.net
      link
      fedilink
      English
      arrow-up
      5
      ·
      2 days ago

      Without having read it myself, perhaps they mean 5% of total usage. So the gas generation is built to be able to handle 2/3rds of the power demand, in case of outage as a backup, but in normal operation will only contribute 5% of the energy demand. That way, in the event of a failure of the renewable energy source for whatever reason, or a failure in the batteries, the gas can kick in and keep the servers online while cutting disposal operations that represent 1/3 of the total.

    • humanspiral@lemmy.ca
      link
      fedilink
      English
      arrow-up
      1
      ·
      1 day ago

      Extreme incompetence in modeling. the github is complete crap. otoh their angelfire site does actually list some costs for the SMR.

      They make the SMR side look absurdly cheap. $55/mwh power costs with 30c/watt capital costs is just absurdly low. Conservative SMR power estimates start at $180/mwh, and so actual microgrid costs would be over 80% lower.

      More incompetence has their microgrid using off shore wind which is just stupid for HVDC requirement for small scale. Automatically too incompetent to trust their modeling. They don’t specify cost assumptions for any of the microgrid components.

      • Aatube@kbin.melroy.org
        link
        fedilink
        arrow-up
        1
        ·
        1 day ago

        wdym the github is complete crap? it has everything you mentioned you wanted to look at. and wouldn’t a too-low estimate for nuclear costs give extra validity to the claim that microgrids are much cheaper?

        • humanspiral@lemmy.ca
          link
          fedilink
          English
          arrow-up
          1
          ·
          1 day ago

          what is .nc file format? their csv data has no cost numbers.

          wouldn’t a too-low estimate for nuclear costs give extra validity to the claim that microgrids are much cheaper?

          It is much cheaper. Everywhere. But the modeling done in this instance can still be completely incompetent.

            • humanspiral@lemmy.ca
              link
              fedilink
              English
              arrow-up
              2
              ·
              21 hours ago

              https://github.com/ryanjenkinson/data-centre-modelling/blob/main/notebooks/model.ipynb does give model details, but doesn’t use that cost file directly.

              some mistakes…

              inflates 2021 costs to 2025 for all technologies. Solar has depreciated, and wind maybe did not go up in price. A bigger deal is no distribution costs. Offshore tall AF wind turbines are cheapest power in the world, if you build an island/raft at the bottom of the turbine to drink the power, and that is only scenario where they are part of a microgrid. They cost much higher than solar due to HVDC lines, and transformers to use “normal” current. Current conversion equipment in general also not included.

              The gas costs overall are very low. Ridiculously low is fixed opex 1/4 that of wind. insurance about the same as solar, when people can get burned or poisoned “easily”, and mile wide craters have occurred at gas plants. No fuel delivery markups on futures prices, or infrastructure costs to deliver it. If it’s going to be 5%-20% capacity factor, delivery by truck is no infrastructure, but high fuel costs. Fuel delivery/handling for low capacity use makes coal look better. Fixed opex requires people operating 24 hours and emergency shutoff standy people.

              Battery modeling is bad. Model uses constraint/linear programming to find a mix, but battery range is capped at 600mwh, with wind and solar at 2000mw, and so can fill battery in 20 minutes. Claim that at 600mwh, you only need gas for 5% of power, makes a gas plant a complete absurdity relative to a utility grid connection. A good battery size is 2 times the maximum charge rate.

              SMR modeling is extreme joke. Based on 540mw reactor which simply is not even SMR. Normal big reactors are 1gw. They save substantial costs by having 4 to 8 on a site. The $55/mwh ($80 in 2025) figure from earlier is just variable/fuel costs. $5/watt construction costs not serious. no reason to ever expect under $15/watt. Neither of the numbers scale down to 120mw either, and nuclear is simply not a 24/7/365 capable energy source, even if you want your datacenter to be. If you need 12 hour maintenance windows, you need 1440mwh of battery systems that you will hardly every use. Nuclear was always stupid to consider, and a grid connection with possible exporting generation assets on site is the way to go.

              Capacity factors for wind of 0.61 is high due to invalid offshore use. With 1400mw wind, and over 800mw wind per hour, a 120mw datacenter is horribly mismatched. Solar of 0.11 is 2.5 hours/day production. It’s a reason to have datacenter outside of UK, but onshore/onsite wind+solar can work for the right UK site. Solar for “off grid” in north should go for lower total capacity factor by maximizing tilt for winter production. Easy to get a full day’s power 9 months of the year, and find way to monetize surpluses. Grid exchange for datacenter application, smart. For datacenters, all electronics run on DC, which means they can all run off batteries, and everything else charges batteries.

              The starting point with behind the meter renewable power with bidirectional grid connection is production required for maximum use + export on a 120mw transmission line per day = 5800mwh. 2600mwh battery to discharge up to 120mw all day is also 24 hours of operation power. Summer solar in UK will reach 8 hour days, and many 7 hour days. Onshore Wind averages 6 hours, but can hit 20 hours in a day. Model is $1.5m/mw wind, and $500k/mw solar (excluding grid connections) at capacity factors favours more solar. Natural DC power also favours solar. Wind has less land footprint, and could benefit from being on the north side, with (idk) solar panels helping rare south winds funnel up to the blades. The winter capacity factors are much higher for wind, and worth more than 3x the cost in winter. Other factors is export value of our electricity. A renewable future means higher night prices, and even in UK, higher winter prices. 24 hour huge battery means profit from day 2, 3 day ahead forecasts arbitrage.

              The right model is 7 hours solar + 6 hours wind = 5800mwh (summer peak). and 6 hours wind + 1 hour solar = 1300mwh which is hoping for 50% self generation in bad solar winter days, but average wind. 200mw of wind and 650mw of solar at winter optimized angle gives 1850mwh on bad solar average wind winter day, and the 5800mwh summer maximum on mnay days with some curtailment possibility. up front power costs are $390m batteries, $325m solar, $350m wind = $1.065B. Over 1twh non curtailed self production per year. For 10% ROI on power production (nevermind datacenter companies having 5% cost of capital), $100/mwh is both export revenue needed and cost of internal power (which if you only needed 5% ROI/or financing burden is $50/mwh). This is lower internal costs than grid or just variable SMR power costs, and can often undercut competing supply for even higher profit. This is same annual production as 120mw 24/7 SMR, but that has $1.8B+ capital costs, and $180/mwh breakeven energy value (before the extreme variable/fixed operating costs). A 120mw fossil plant does mean just $30/mwh capital cost retrieval, but the operational costs are at least $60/mwh. OP Model underscores these heavily. The renewables approach achieves lower internal power costs + big profit opportunity from electricity trade. The variable costs of fossil fuel plants means they can’t just run 24/7 into a market price that loses them money, and so it only makes sense for datacenter to not share fossil power with rest of society.

                • humanspiral@lemmy.ca
                  link
                  fedilink
                  English
                  arrow-up
                  1
                  ·
                  10 hours ago

                  https://en.wikipedia.org/wiki/NuScale_Power is the epitomy of scams in US/western nuclear and political corruption. SMRs are a new scam because larger units are unbankable and proven failures. The science for a theoretical on budget process makes SMRs more costly, even though the on budget time/costs of nuclear is not economic to begin with anymore.

                  NuScale SMR is about combining up to 12 77mwe reactors for your totals. It is up to budgets of $20/watt with variable costs of $120/mwh with still a handful of years to go before first completion. Vogtle spent a decade with a 3 year completion target, and budget doubled during that decade. They ended with $17/watt construction costs. SMRs also cheat on build costs by requiring ultra enriched (expensive/scary plutonium equivalent) fuel that is scarce without new build of military focused breeder/traditional reactors to provide adequate supply.